Individual room controller - software
In case of XMP-GA-IRC communication failure the XMP-GA-BOX32/IRC will transmit an alarm message to the host system.
Up to 10 occupation times per day can be set.
Contacts can be used for:
- Dew-point low value
- Window open
- Person(s) present yes/no
- Light on/off
- Fire protection flap released
- Sun blinds down/up etc.
Blocking the cooling sequence and/or heating sequence in case of dew point reached.
The XMP-GA-IRC can manage four operation modes:
- Economy operation
- Stand-by operation
- Comfort operation
- Cool down protection
Presence push-button or presence messenger are possible.
The comfort set-point temperature can be varied, for example, in a range of ±4°C around a middle comfort set-point temperature (for example 21°C) which also can be set.
Up to 10 comfort operation time windows can be set in the Babylon system.
With the XMP-GA-IRC the configuration of a P-controller or a PI-controller is possible.